Installation site
|
outdoor
|
Ambient temperature
|
-25ºC~+40ºC
|
Max. daily temperature difference
|
≤25ºC
|
Height above sea level
|
2000m(no limit for specified order)
|
Air humidity
|
Daily average:≤95%;
month average:≤90%; |
Wind speed
|
≤34m/s
|
Solar radiation
|
≤0.1W/cm2(fine day, noon)
|
Earthquake intensity
|
horizontal:≤0.3g;vertical:≤0.15g
|
Icing thickness
|
≤10mm
|
Creepage distance
|
25mm/kV or 31mm/kV
|
Static load on terminal in Y-direction
|
1250N
|
Static load on terminal in X-direction
|
750N
|
Static load on terminal in Z-direction
|
1000N
|
No.
|
Items
|
Unit
|
Parameter
|
||
1
|
Rated voltage
|
kV
|
126
|
||
2
|
Rated power frequency withstand voltage(1min)
|
Phase-to-phase
Phase-to-ground |
kV
|
230
|
|
fracture
|
kV
|
230+73*
|
|||
3
|
Rated lightning impulse withstand voltage
|
Phase-to-phase
Phase-to-ground |
kV
|
550
|
|
fracture
|
kV
|
550+103*
|
|||
4
|
Power frequency withstand voltage(5min)under SF6 zero-gauge pressure
|
kV
|
Send your message to us
|